Vana Sızdırmazlık Sınıfları
Types of Leakage
There are two types of leakage from a valve,
- External Leakage: Fugitive emissions from the valve to atmosphere
- Internal Leakage: Leakage through the valve but contained within the piping system
Reasons of the Leakage
First of all , the right valve type and materials should be selected by considering the process and applciation details . Note that most of the leakage problems occur because of wrong selection of valve type or materials.
Common causes of leakage to atmosphere:
Gasket between valve-body and valve-bonnet is damaged
Common causes of leakage through the valve
Valve is not fully closed
This can be due to various reasons, including;
Valve seat is prevented from closing fully due to dirt, rust, or line debris
Insufficient actuator travel
The seat is damaged
The seal is damaged
American Petroleum Institute (API)
The American Petroleum Institute API598: Valve Inspection and Testing,
covers the testing and inspection requirements for gate, globe, check, ball, plug & butterfly valves.
It has acceptable leakage rates for liquid as well as gas testing.
All valves built to the various API standards are required to meet API-598 leakage criteria prior to shipment .
API 598 states for shell and backseat tests, no visible leakage is permitted.
If the fluid is a liquid, there shall be no visible evidence of drops or wetting of the external surfaces
(no visible leakage through the body, body liner, if any, and body-to-bonnet joint and no structural damage).
The allowable rate for leakage of test fluid past the seats, for the duration of the tests, is listed in the following table:
- There shall be no leakage for the minimum specified test duration. For liquid test, 0 drop means no visible leakage per minimum specified test duration. For gas test, 0 bubble means less then 1 bubble per minimum specified test duration.
- The maximum permissible leakage rate shall be 0.18 cubic inch (3 cubic centimeters) per minute per inch of nominal pipe size.
- The maximum permissible leakage rates shall be 1.5 standard cubic feet (0.042 cubic meter) of gas per hour per inch of nominal pipe size.
Manufacturer’s Standardisation Society (MSS)
The MSS standard MSS-SP-61: Pressure Testing of Valves was originally adopted in 1961. It was developed for the purpose of providing a uniform means of testing valves commonly used in the “full open” and “full closed” type of service.
It is not intended for use with control valves. Refer to standard ANSI/FCI 70-2 for Control Valves.
Pressure Testing of Steel Valves, relates to seat closure tests, and defines the following leakage rates:
Gate, Globe, Ball valves
10 cc/hr per inch of nominal pipe diameter
(Example: A 6″ globe valve is allowed to leak 60 cc/hr in a test)
Check valves
40 cc/hr per inch of nominal pipe diameter
All shutoff or isolation valves specified to MSS-SP-61 must pass the above standards.
American National Standards Institute (ANSI)
The ANSI standard FCI 70-2: Control Valve Seat Leakage,
establishes a series of six seat leakage classes for control valves and defines the test procedures.
Class I. Is also know as dust tight and can refer to metal or resilient seated valves,
no actual shop test is made.
Class II. This class establishes the maximum permissible leakage generally associated with commercial double-seat control valves or balanced single-seat control valves with a piston ring seal and metal-to-metal seats.
0.5% leakage of full open valve capacity
Service dP or 50 psid (3.4 bar differential), whichever is lower at 50 to 125 oF
Test medium air at 45 to 60 psig is the test fluid
Class III. This class establishes the maximum permissible leakage generally associated with Class II (4.2.2),
but with a higher degree of seat and seal tightness.
0.1% leakage of full open valve capacity
Service dP or 50 psid (3.4 bar differential), whichever is lower at 50 to 125 oF
Test medium air at 45 to 60 psig is the test fluid
Class IV. This class establishes the maximum permissible leakage generally associated with commercial unbalanced single-seat control valves and balanced single-seat control valves with extra tight piston rings or other sealing means and metal-to-metal seats.
0.01% leakage of full open valve capacity
Service dP or 50 psid (3.4 bar differential), whichever is lower at 50 to 125 oF
Test medium air at 45 to 60 psig is the test fluid
Class V. This class is usually specified for critical applications where the control valve may be required to be closed, without a blocking valve, for long periods of time with high differential pressure across the seating surfaces.
It requires special manufacturing, assembly and testing techniques. This class is generally associated with metal seat, unbalanced single-seat control valves or balanced single-seat designs with exceptional seat and seal tightness.
The test fluid is water at 100 psig or operating pressure
Leakage allowed is limited to 5 x 10-4 ml per minute per inch of orifice diameter per psi differential
Service dP at 50 to 125 oF
CLASS VI. This class establishes the maximum permissible seat leakage generally associated with resilient seating control valves either unbalanced or balanced single-seat with “O” rings or similar gapless seals.
The test fluid is air or nitrogen
Pressure is the lesser of 50 psig or operating pressure
The leakage limit depends on valve size and ranges from 0.15 to 6.75 ml per minute for valve sizes 1 through 8 inches, please check the below table for further details.
Port Diameter |
Bubbles per minute |
ml per minute |
|
inches |
mm |
||
1 |
25 | 1 | 0.15 |
1 1/2 |
38 | 2 |
0.30 |
2 | 51 | 3 |
0.45 |
2 1/2 |
64 | 4 | 0.60 |
3 |
76 |
6 |
0.90 |
4 |
102 | 11 | 1.70 |
6 |
152 | 27 |
4.00 |
8 | 203 | 45 |
6.75 |
10 | 254 | 63 |
9 |
12 | 305 | 81 |
11.5 |
Control Valve Leakage Classification Overview
as per ANSI Standard FCI 70-2
Leakage Class Designation |
Maximum Leakage Allowable | Test Medium | Test Pressure | Testing Procedures Required for Establishing Rating |
I |
x | x | x |
No test required |
II | 0.5% of rated capacity | Air or water at 50 – 125oF (10 – 52oC) |
45 – 60 psig or maximum operating differential whichever is lower |
45 – 60 psig or maximum operating differential whichever is lower |
III |
0.1% of rated capacity | As above | As above | As above |
IV | 0.01% of rated capacity | As above | As above |
As above |
V |
0.0005 ml per minute of water per inch of port diameter per psi differential | Water at 50 to125oF (10 to 52oC) | Maximum service pressure drop across valve plug not to exceed ANSI body rating |
Maximum service pressure drop across valve plug not to exceed ANSI body rating |
VI | Not to exceed amounts shown in the table above | Air or nitrogen at 50 to 125o F (10 to 52oC) | 50 psig or max rated differential pressure across valve plug whichever is lower |
Actuator should be adjusted to operating conditions specified with full normal closing thrust applied to valve plug seat |
International Organization for Standardization (ISO)
The purpose of ISO standard 5208: Industrial valves – Pressure testing of metallic valves,
is the establishment of basic requirements and practices for pressure testing valves of various configurations that are used in general purpose, power generation, petroleum, and petrochemical or allied industry applications.
The intent is to provide a consistent set of procedural requirements and acceptance criteria that can be considered in conjunction with valve specific standards appropriate for specific applications.
Account has been taken of the valve testing requirement needs of EN 12266 and API 598 with requirements referenced for PN designated valves for the former and Class designated valves for the latter.
MAXIMUM ALLOWABLE CLOSURE TEST LEAKAGE AS PER ISO 5208 | |||||||||||
TEST FLUID |
UNIT LEAKAGE RATES |
RATE A |
RATE AA |
RATE B |
RATE C |
RATE CC |
RATE D |
RATE E |
RATE EE |
RATE F |
RATE G |
LIQUID
|
MM3/S | (1) | 0.006
X DN |
0.01
X DN |
0.03
X DN |
0.08
X DN |
0.1
X DN |
0.3
X DN |
0.39
X DN |
1
X DN |
2
X DN |
DROPS/S | 0.0001
X DN |
0.00016
X DN |
0.0005
X DN |
0.0013
X DN |
0.0016
X DN |
0.0048
X DN |
0.0062
X DN |
0.016
X DN |
0.032
X DN |
||
GAS
|
MM3/S | (1) | 0.18
X DN |
0.3
X DN |
3
X DN |
22.3
X DN |
30
X DN |
300
X DN |
470
X DN |
3000
X DN |
6000
X DN |
BUBBLES/S | 0.003
X DN |
0.0046
X DN |
0.0458
X DN |
0.3407
X DN |
0.4584
X DN |
4.5837
X DN |
7.1293
X DN |
45.837
X DN |
91.673
X DN |
Notes:
The leakage rates only apply when discharging test fluid to the atmosphere.
The meaning of “No visually detectable leakage” is that there is no visible weeping or leakage in the form of drops or bubbles.
There is a loosely defined correspondence between the leakage rate acceptance values of API 598
and the leakage values Rate A as applied to DN ≤50, Rate AA-Gas and Rate CC-Liquid for other than metal seated check valves
and for check valves Rate EE-Gas and Rate G-Liquid. Rates A, B, C, D E, F and G correspond to values in EN 12266-1.
PRESSURE TESTS AS PER ISO 5208 | ||||||||
TEST TYPE | PN or CLASS | GATE VALVE | GLOBE VALVE | PLUG VALVE (A) | CHECK VALVE | FLOATING BALL OR DIAPHRAGM VALVE | BUTTERFLY OR TRUNNION MOUNTED BALL VALVE | |
SHELL TEST LIQUID | ALL | ALL | REQUIRED | REQUIRED | REQUIRED | REQUIRED | REQUIRED | REQUIRED |
SHELL TEST GAS | ALL | ALL | OPTIONAL | OPTIONAL | OPTIONAL | OPTIONAL | OPTIONAL | OPTIONAL |
BACKSEAT TEST (B, C) LIQUID | ALL | ALL | OPTIONAL | OPTIONAL | NOT REQUIRED | NOT REQUIRED | NOT REQUIRED | NOT REQUIRED |
CLOSURE
TEST GAS LOW- PRESSURE |
DN
≤ 100 |
CLASS ≤ 1500 | REQUIRED | OPTIONAL | REQUIRED | OPTIONAL | REQUIRED | REQUIRED |
AND | ||||||||
PN ≤ 250 | ||||||||
CLASS | OPTIONAL | OPTIONAL | OPTIONAL | OPTIONAL | REQUIRED | OPTIONAL | ||
>1500 | ||||||||
AND | ||||||||
PN >250 | ||||||||
DN
>100 |
CLASS | REQUIRED | OPTIONAL | OPTIONAL | OPTIONAL | REQUIRED | REQUIRED | |
≤ 600 | ||||||||
AND | ||||||||
PN ≤ 100 | ||||||||
CLASS | OPTIONAL | OPTIONAL | OPTIONAL | OPTIONAL | REQUIRED | OPTIONAL | ||
>600 | ||||||||
AND | ||||||||
PN >100 | ||||||||
CLOSURE
TEST LIQUID HIGH- PRESSURE |
DN
≤ 100 |
CLASS | OPTIONAL | REQUIRED | OPTIONAL | REQUIRED | OPTIONAL | OPTIONAL |
≤ 1500 | ||||||||
AND | ||||||||
PN ≤ 250 | ||||||||
CLASS | REQUIRED | REQUIRED | REQUIRED | REQUIRED | OPTIONAL | REQUIRED | ||
>1500 | ||||||||
AND | ||||||||
PN >250 | ||||||||
DN
>100 |
CLASS | REQUIRED | REQUIRED | OPTIONAL | REQUIRED | OPTIONAL | OPTIONAL | |
≤ 600 | ||||||||
AND | ||||||||
PN ≤ 100 | ||||||||
CLASS | REQUIRED | REQUIRED | REQUIRED | REQUIRED | OPTIONAL | REQUIRED | ||
>600 | ||||||||
AND | ||||||||
Inspection & Testing in accordance with BS EN 12266 – 1
Shell Test (Body Hydro Test):
Test pressure for each valve shall be a minimum of 1.5 times the allowable pressure at room temperature.
Test media: – Shell test shall be made with water contain corrosion or rust inhibitor.
Acceptance Criteria: – Visually detectable leakage from any external surface of the shell is not permitted.
Leakage from the operating mechanism sealing is permitted at the shell test pressure provided that there is no visual detectable leakage when the test pressure is 1.1 times the allowable pressure at room temperature.
Minimum Test Duration for Shell Tests | ||
Nominal Size |
Production Test & Acceptance Test (s) |
Type Test ( min ) |
Up to DN 50 |
15 |
10 |
From DN 65 to DN 200 |
60 |
10 |
DN 250 & above |
180 |
10 |
Inspection & Testing in accordance with EN 12266 – 1
Seat Tightness Test :
Test pressure shall be a minimum of 1.1 times the allowable differential pressure at room temperature,
except that if the test fluid is gas, the test pressure may be lower of 1.1 times the allowable differential pressure at room
temperature or ( 6± 1) bar for valves:
Size up to DN 80 for all pressure ratings
Size above DN80 & up to DN200 for pressure ratings up to PN40 & up to Class300.
Minimum Test Duration for Seat Tightness Tests | ||||
Nominal Size | Production Test & Acceptance Test | Type Test | ||
Metal Seated Valves | Soft Seated valves | All Valves | ||
Liquid | Gas | Liquid or Gas | Liquid or Gas | |
Up to DN 50 | 15s | 15s | 15s | 10min |
DN 65 to DN 200 | 30s | 15s | 15s | 10min |
DN 250 to DN 450 | 60s | 30s | 30s | 10min |
DN 500 & above | 120s | 30s | 60s | 10min |
Acceptance Criteria: – As per below table.
Maximum Allowable Seat Leakage for each leakage rate in cubic millimeters per second | |||||||
Test Fluid | Rate A | Rate B | Rate C | Rate D | Rate E | Rate F | Rate G |
Liquid | No visually detectable leakage | 0.01 x DN | 0.03 x DN | 0.1 x DN | 0.3 x DN | 1.0 x DN | 2.0 x DN |
Gas | 0.3 x DN | 3.0 X DN | 30 x DN | 300 x DN | 3000 x DN | 6000 xDN |